Signal Conditioning and Data Acquisition System

117603
Back to Signal Conditioning and Data Acquisition System

Module 2: Signal Conditioning Systems

  1. Q1(a). A signal conditioner may be used to: (i) Generate source code (ii) Replace a transducer (iii) Filter unwanted components (iv) Store files20262m

    Module 2: Signal Conditioning Systems

    A signal conditioner may be used to:

    (i) Generate source code
    (ii) Replace a transducer
    (iii) Filter unwanted components
    (iv) Store files

    View this question on its own page →
    Worked Solution

    Answer: (iii) Filter unwanted components

    A signal conditioner prepares a sensor signal for the ADC by amplifying, filtering, isolating and linearizing it. It does not replace the transducer or store files.

  2. Q1(b). Signal conditioning is required to: (i) Improve computer speed (ii) Modify the sensor signal for ADC (iii) Reduce sampling time (iv) Increase AC voltage2025?m

    Module 2: Signal Conditioning Systems

    Signal conditioning is required to:
    (i) Improve computer speed
    (ii) Modify the sensor signal for ADC
    (iii) Reduce sampling time
    (iv) Increase AC voltage

    View this question on its own page →
    Worked Solution

    Answer

    Correct option: (ii) Modify the sensor signal for ADC

    Explanation

    Signal conditioning prepares a raw sensor signal so that it is suitable for accurate measurement and conversion by an ADC.

    Common signal-conditioning operations include:

    • Amplification – increases a weak sensor signal.
    • Filtering – removes unwanted noise and interference.
    • Isolation – protects circuits and reduces ground-loop problems.
    • Linearization – improves the relationship between sensor output and measured quantity.
    • Level shifting – adjusts the signal to the ADC input range.

    For example, if a sensor produces 0–100 mV while an ADC accepts 0–5 V, an amplifier can increase the sensor signal before conversion.

    Therefore, the correct answer is (ii).

  3. Q1(c). Filtering is mainly used to remove: (i) Useful signals (ii) High-frequency noise (iii) DC (iv) Mechanical vibrations2025?m

    Module 2: Signal Conditioning Systems

    Filtering is mainly used to remove:
    (i) Useful signals
    (ii) High-frequency noise
    (iii) DC
    (iv) Mechanical vibrations

    View this question on its own page →
    Worked Solution

    Answer

    Correct option: (ii) High-frequency noise

    Explanation

    A filter is a signal-conditioning circuit that allows desired frequency components to pass while attenuating unwanted frequency components.

    In DAQ systems, filters are commonly used to remove high-frequency noise, electrical interference and other unwanted components before the signal reaches the ADC.

    For example, a low-pass filter allows low-frequency measurement signals to pass while reducing high-frequency noise.

    Importance in DAQ

    Filtering improves:

    1. Signal quality.
    2. Measurement accuracy.
    3. ADC performance.
    4. Resistance to unwanted interference.
    5. Protection against aliasing when used as an anti-aliasing filter before sampling.

    Therefore, the correct answer is (ii).

  4. Q1(d). A first-order filter consists of: (i) One resistor and one capacitor (ii) Two inductors (iii) Operational amplifier only (iv) A transformer2025?m

    Module 2: Signal Conditioning Systems

    A first-order filter consists of:
    (i) One resistor and one capacitor
    (ii) Two inductors
    (iii) Operational amplifier only
    (iv) A transformer

    View this question on its own page →
    Worked Solution

    Answer

    Correct option: (i) One resistor and one capacitor

    Explanation

    A basic first-order RC filter is made using one resistor and one capacitor. It has one energy-storage element and therefore has a roll-off of approximately 20 dB/decade beyond its cutoff frequency.

    For a simple RC low-pass filter, the cutoff frequency is:

    fc=12πRCf_c = \frac{1}{2\pi RC}

    Below the cutoff frequency, the signal passes with relatively little attenuation. Above the cutoff frequency, higher-frequency components are increasingly attenuated.

    Therefore, the correct answer is (i).

  5. Q1(d). Aliasing occurs when a signal is sampled: (i) After amplification (ii) At twice its frequency (iii) Below the required sampling rate (iv) With a low-pass filter20262m

    Module 2: Signal Conditioning Systems

    Aliasing occurs when a signal is sampled:

    (i) After amplification
    (ii) At twice its frequency
    (iii) Below the required sampling rate
    (iv) With a low-pass filter

    View this question on its own page →
    Worked Solution

    Answer: (iii) Below the required sampling rate

    If sampling frequency is less than twice the highest signal frequency (Nyquist), high-frequency components appear as false lower frequencies. This is aliasing.

  6. Q1(e). The Nyquist rate should be at least: (i) Equal to the signal frequency (ii) Half the signal frequency (iii) Four times the sampling period (iv) Twice the highest signal frequency20262m

    Module 2: Signal Conditioning Systems

    The Nyquist rate should be at least:

    (i) Equal to the signal frequency
    (ii) Half the signal frequency
    (iii) Four times the sampling period
    (iv) Twice the highest signal frequency

    View this question on its own page →
    Worked Solution

    Answer: (iv) Twice the highest signal frequency

    Nyquist criterion: fs≥2fmaxf_s \ge 2 f_{max}. Sampling at or above this rate allows the signal to be reconstructed without aliasing.

  7. Q2(b). Describe the signal conditioning process in a DAQ system and explain how it is used in real-time applications.20257m

    Module 2: Signal Conditioning Systems

    Describe the signal conditioning process in a DAQ system and explain how it is used in real-time applications.

    View this question on its own page →
    Worked Solution

    Solution: Signal Conditioning Process and Real-Time Applications

    Definition

    Signal conditioning is the process of modifying a sensor's raw electrical output so that it becomes suitable for accurate measurement, analog-to-digital conversion, processing, and control.

    A typical chain is:

    Sensor → Amplification → Filtering → Isolation / Linearization → ADC → Processor
    

    Why Signal Conditioning is Required

    Sensor outputs are often:

    • Very small in amplitude.
    • Noisy.
    • Non-linear.
    • Outside the input range of the ADC.
    • Sensitive to electrical interference.
    • Referenced to a different ground potential.

    Signal conditioning solves these problems before digitization.

    Major Signal-Conditioning Operations

    1. Amplification

    A weak sensor signal is amplified to use the available ADC input range effectively.

    For an amplifier:

    Vout=GVinV_{out}=G V_{in}

    where GG is the voltage gain.

    2. Filtering

    Filters remove unwanted frequency components and noise.

    A low-pass filter is commonly placed before an ADC to remove high-frequency noise and prevent aliasing.

    For a first-order RC low-pass filter:

    fc=12πRCf_c=\frac{1}{2\pi RC}

    3. Isolation

    Isolation electrically separates the sensor side from the measurement electronics. It helps protect circuits and reduce ground-loop interference.

    Common techniques include transformers, opto-isolators and isolation amplifiers.

    4. Linearization

    Some sensors have non-linear output characteristics. Linearization converts the sensor response into a more useful relationship with the measured physical quantity.

    This may be performed using analog circuits or digitally in the microcontroller.

    5. Level Shifting and Scaling

    The signal is adjusted to match the ADC input range.

    For example, if a sensor produces 0–100 mV and the ADC accepts 0–5 V, an amplifier can scale the signal so that the ADC uses more of its resolution.

    6. Excitation

    Some sensors such as resistive bridges require an excitation voltage or current. The signal-conditioning system may provide this excitation and measure the resulting response.

    Real-Time DAQ Applications

    Temperature Monitoring

    Temperature Sensor → Amplifier/Filter → ADC → Microcontroller → Display/Alarm
    

    The microcontroller continuously samples the sensor and can activate an alarm if temperature exceeds a limit.

    Motor-Speed Monitoring

    A speed sensor produces pulses proportional to motor speed. Conditioning removes noise and shapes the pulses before the microcontroller counts them.

    Heart-Rate Monitoring

    A biomedical sensor produces a small physiological signal. Amplification and filtering remove unwanted noise and interference. The conditioned signal is digitized and processed to calculate heart rate.

    Importance in Real-Time Systems

    Proper signal conditioning provides:

    1. Better measurement accuracy.
    2. Improved signal-to-noise ratio.
    3. Protection of ADC and processing electronics.
    4. Better use of ADC resolution.
    5. Reliable real-time decision-making.
    6. Reduced aliasing and interference.

    Conclusion

    Signal conditioning is a critical stage between the sensor and ADC. By amplifying, filtering, isolating, scaling and linearizing the sensor signal, it ensures that the DAQ system receives a clean and measurable signal suitable for reliable real-time monitoring and control.

  8. Q3. Explain the different types of signal conditioning used in data acquisition systems.20257m

    Module 2: Signal Conditioning Systems

    Explain the different types of signal conditioning used in data acquisition systems.

    View this question on its own page →
    Worked Solution

    Solution: Types of Signal Conditioning in DAQ Systems

    Signal conditioning prepares a sensor signal for accurate measurement and ADC conversion.

    1. Amplification

    Weak sensor outputs are increased to a suitable voltage range.

    Vout=GVinV_{out}=G V_{in}

    Operational amplifiers and instrumentation amplifiers are commonly used.

    2. Filtering

    Filters remove unwanted frequency components and noise.

    • Low-pass: removes high-frequency noise.
    • High-pass: removes unwanted low-frequency/DC components.
    • Band-pass: passes a selected frequency band.
    • Notch: rejects a narrow interfering frequency such as 50/60 Hz.

    3. Isolation

    Electrical isolation prevents unwanted current paths and protects the measurement system. Isolation amplifiers and opto-isolators are common methods.

    4. Linearization

    Some sensors have nonlinear input-output characteristics. Linearization converts the response into a more convenient relationship, either using analog circuits or software.

    5. Level Shifting and Scaling

    The signal is shifted or scaled to match the ADC input range. For example, a 0–100 mV sensor can be amplified to 0–5 V.

    6. Excitation

    Resistive and bridge-type sensors may require a stable excitation voltage or current before their output can be measured.

    7. Signal Conversion

    A conditioning stage may convert one signal form to another, such as current-to-voltage conversion for a 4–20 mA transmitter.

    8. Sample-and-Hold / Anti-Aliasing

    A sample-and-hold circuit maintains the signal during conversion, while an analog anti-aliasing filter limits frequencies above the useful measurement bandwidth.

    Conclusion

    The major conditioning functions are amplification, filtering, isolation, linearization, scaling, excitation and signal conversion. Proper conditioning improves signal-to-noise ratio, ADC utilization, accuracy and reliability.

  9. Q3(a). Discuss the need for signal conditioning. Describe amplification, attenuation, isolation and linearization.20267m

    Module 2: Signal Conditioning Systems

    Discuss the need for signal conditioning. Describe amplification, attenuation, isolation and linearization.

    View this question on its own page →
    Worked Solution

    Need for Signal Conditioning

    Sensor outputs are usually small (mV), noisy, non-linear, or at levels the ADC cannot accept directly. Signal conditioning converts them into a clean signal that matches the ADC input range.

    MermaidDiagram
    Rendering diagram…

    Needs

    1. Weak signals must be amplified.
    2. Noise and interference must be removed.
    3. Protection from high voltages and ground loops.
    4. Sensor non-linearity must be corrected.
    5. Match ADC input range and impedance.

    Amplification

    Increases signal level, e.g. thermocouple mV to 0-5 V. An instrumentation amplifier is preferred for bridges because of high input impedance and high CMRR. Gain: G=1+2Rf/RgG = 1 + 2R_f/R_g (3 op-amp in-amp).

    Attenuation

    Reduces large signals to the ADC range, using a resistor divider: Vout=Vin R2/(R1+R2)V_{out}= V_{in}\,R_2/(R_1+R_2).

    Isolation

    Electrically separates the sensor side from the DAQ side using optocouplers, transformers or isolation amplifiers. It prevents ground loops, protects the patient and equipment, and rejects common-mode voltage.

    Linearization

    Corrects a non-linear sensor response (thermistor, thermocouple) using analog circuits, look-up tables or polynomial equations in software, so output is proportional to the measured quantity.

    Function Purpose
    Amplification Raise small signals
    Attenuation Bring large signals into range
    Isolation Safety, no ground loops
    Linearization Proportional output

    Exam tip

    Mention the in-amp for amplification, optocoupler for isolation and look-up table for linearization.

  10. Q3(b). Compare plug-in boards, direct-connect modules, two-wire transmitters and distributed I/O arrangements.20267m

    Module 2: Signal Conditioning Systems

    Compare plug-in boards, direct-connect modules, two-wire transmitters and distributed I/O arrangements.

    View this question on its own page →
    Worked Solution

    Signal Conditioning Arrangements

    MermaidDiagram
    Rendering diagram…
    Feature Plug-in boards Direct-connect modules Two-wire transmitters Distributed I/O
    Location Inside PC slot External module wired to the DAQ Mounted near sensor Remote nodes on a network
    Output Raw digital via PC bus Conditioned analog or digital 4-20 mA current loop Digital over RS-485 or Ethernet
    Distance Short Short to medium Long (hundreds of metres) Very long
    Noise immunity Low (inside PC) Medium High (current signal) High
    Channels Limited by slots Moderate One per transmitter Many nodes
    Cost Low Medium Medium High
    Use Lab setups Industrial measurement Process control Large plants

    Key points

    • Plug-in boards: ADC plus conditioning on a card in the computer; fast, but noisy PC environment.
    • Direct-connect modules: sensor connects to a conditioning module (e.g. SCXI-type) which then connects to the DAQ.
    • Two-wire transmitters: the same two wires carry power and the 4-20 mA signal; live zero (4 mA) allows wire-break detection.
    • Distributed I/O: remote units digitize locally and send data over a network, avoiding long analog runs.

    Exam tip

    A comparison table like the above gets full marks; mention 4-20 mA.

  11. Budget App•POCKETLY

    Pocketly on Android

    Log daily food, travel, and hostel expenses instantly. Set monthly spending limits and see where your money goes without complex spreadsheets.

    Install Pocketly
  12. Q4(a). Describe the various noise sources and noise reduction techniques in signal measurement systems.20257m

    Module 2: Signal Conditioning Systems

    Describe the various noise sources and noise reduction techniques in signal measurement systems.

    View this question on its own page →
    Worked Solution

    Solution: Noise Sources and Noise Reduction Techniques

    Noise

    Noise is an unwanted electrical signal that interferes with the desired measurement signal and reduces measurement accuracy.

    Major Noise Sources

    1. Thermal Noise

    Produced by random motion of charge carriers in resistive components. Its noise power increases with temperature and bandwidth.

    2. Shot Noise

    Caused by the random arrival of charge carriers, especially in semiconductor devices and junctions.

    3. Flicker Noise

    Also called 1/f noise. It becomes important at low frequencies and is associated with electronic devices and materials.

    4. Electromagnetic Interference (EMI)

    Motors, transformers, switching circuits, mobile/radio transmitters and power lines can induce unwanted signals.

    5. Ground Loops

    Different ground potentials can create unwanted circulating currents and 50/60 Hz interference.

    6. Crosstalk

    A signal from one channel can couple into another through electrical or electromagnetic coupling.

    7. Quantization Noise

    Introduced when an analog value is represented by a finite number of ADC levels.

    Noise Reduction Techniques

    1. Shielding

    Use shielded cables and conductive enclosures to reduce electromagnetic pickup.

    2. Proper Grounding

    Use a carefully designed grounding scheme and avoid unnecessary ground loops.

    3. Twisted-Pair Cables

    Twisting reduces pickup from external electromagnetic fields, especially for differential signals.

    4. Differential Measurement

    Measure the voltage difference between two signal terminals rather than relying on a common ground reference. This improves rejection of common-mode interference.

    5. Filtering

    Use low-pass, high-pass, band-pass or notch filters according to the measurement bandwidth.

    6. Isolation

    Isolation amplifiers, transformers or digital isolators can break unwanted electrical paths.

    7. Short and Proper Wiring

    Keep sensitive signal wires short, route them away from high-power cables and separate analog and noisy digital wiring.

    8. Averaging and Digital Filtering

    Repeated measurements can be averaged, and digital filters can reduce random noise after acquisition.

    Conclusion

    Noise reduction requires a combination of shielding, grounding, differential measurement, filtering, isolation and proper wiring. The best technique depends on the source and frequency of the interference.

  13. Q4(a). What are the common sources of noise in measurement systems? Suggest suitable methods for minimizing noise.20267m

    Module 2: Signal Conditioning Systems

    What are the common sources of noise in measurement systems? Suggest suitable methods for minimizing noise.

    View this question on its own page →
    Worked Solution

    Noise in Measurement Systems

    Noise is any unwanted signal that corrupts the measured signal and reduces the signal-to-noise ratio, SNR=20log⁡(Vs/Vn)SNR = 20\log(V_s/V_n) dB.

    Sources of noise

    MermaidDiagram
    Rendering diagram…
    Source Cause
    Thermal (Johnson) Random motion of electrons in resistors, Vn=4kTRBV_n=\sqrt{4kTRB}
    Shot Discrete charge flow across junctions
    Flicker (1/f) Low-frequency device imperfections
    Power line 50 Hz mains coupling (capacitive or inductive)
    EMI / RFI Motors, relays, radio transmitters
    Ground loop Different ground potentials
    Crosstalk Coupling between adjacent wires

    Methods to minimize noise

    1. Shielding of cables and sensors, grounded at one point.
    2. Twisted-pair wiring so induced noise cancels.
    3. Differential measurement and an instrumentation amplifier with high CMRR.
    4. Filtering: low-pass, notch (50 Hz) and band-pass filters.
    5. Proper grounding (single point) and star ground to avoid loops.
    6. Isolation using optocouplers or isolation amplifiers.
    7. Averaging of repeated samples and lock-in techniques.
    8. Keep signal cables away from power lines; use short leads and low source resistance.

    Exam tip

    Classify as internal and external, give 3 sources and at least 5 remedies.

  14. Q4(b). Explain sampling and aliasing. Discuss the role of anti-aliasing prefilters and compare first-order and second-order filters.20267m

    Module 2: Signal Conditioning Systems

    Explain sampling and aliasing. Discuss the role of anti-aliasing prefilters and compare first-order and second-order filters.

    View this question on its own page →
    Worked Solution

    Sampling and Aliasing

    Sampling converts a continuous signal into discrete values taken every Ts=1/fsT_s = 1/f_s seconds.

    Nyquist theorem: fs≥2fmaxf_s \ge 2 f_{max}. If fs<2fmaxf_s < 2f_{max}, higher frequencies fold back as false lower frequencies. This is aliasing, and it cannot be removed after sampling. Alias frequency: fa=∣f−nfs∣f_a = |f - n f_s|.

    Example: a 700 Hz signal sampled at 1000 Hz appears as 300 Hz.

    SVGVector Architecture Diagram (SVG)
    Aliasing: undersampled signal looks like a slow waveBlue: true signal. Red dots: samples. Red dashed: false (alias) signal

    Anti-aliasing prefilter

    A low-pass filter placed before the ADC removes frequency components above fs/2f_s/2, so aliasing cannot occur. Cut-off is set at or slightly below fs/2f_s/2.

    MermaidDiagram
    Rendering diagram…

    First-order vs second-order filter

    Point First order Second order
    Roll-off 20 dB per decade 40 dB per decade
    Components One R and one C Two R, two C (or op-amp stage)
    Cut-off sharpness Gradual Sharper
    Aliasing rejection Poor, needs high fsf_s Better
    Complexity Simple Moderate
    Use Basic smoothing Practical anti-aliasing

    Exam tip

    State Nyquist, give the alias formula and place the filter before the ADC in the diagram.

  15. Q9(a). Write a short note on: Shielded and twisted-pair cables20267m

    Module 2: Signal Conditioning Systems

    Write a short note on: Shielded and twisted-pair cables

    View this question on its own page →
    Worked Solution

    Short Note: Shielded and Twisted-Pair Cables

    Both reduce electromagnetic interference (EMI) picked up by signal cables.

    Twisted pair

    Two insulated wires twisted together. Interference induces equal voltages in both wires; a differential receiver cancels these (common-mode). Closer twists give better rejection, especially of magnetic fields.

    Shielded cable

    The conductors are surrounded by a metal foil or braid, grounded at one end (normally the signal source end), which blocks electric-field (capacitive) interference and prevents ground loops.

    MermaidDiagram
    Rendering diagram…
    Point Twisted pair Shielded
    Protects against Magnetic and common-mode noise Electric-field noise, RFI
    Cost Low Higher
    Use Ethernet, RS-485 Low-level sensor signals, audio

    Shielded twisted pair (STP) combines both and is used for thermocouples, ECG leads and RS-485.

    Exam tip

    Explain cancellation in twisted pair and single-point grounding of the shield.

  16. Q9(b). A 14-bit ADC (counts 0...16383) is used with an input range of 0...2.500 V to read a temperature sensor whose output is linearly 0–2.5 V (for 0–200°C). During calibration you measure that a known 100°C reference gives an ADC code of 6550. (i) Compute the ideal LSB (in volts) and the ideal code corresponding to 100°C. (ii) From the calibration reading (6550), find the offset error in volts and in °C.20257m

    Module 2: Signal Conditioning Systems

    A 14-bit ADC (counts 0...16383) is used with an input range of 0...2.500 V to read a temperature sensor whose output is linearly 0–2.5 V (for 0–200°C). During calibration you measure that a known 100°C reference gives an ADC code of 6550.
    (i) Compute the ideal LSB (in volts) and the ideal code corresponding to 100°C.
    (ii) From the calibration reading (6550), find the offset error in volts and in °C.

    View this question on its own page →
    Worked Solution

    Solution: ADC Resolution and Calibration Error

    Given:

    • ADC resolution = 14 bits
    • ADC counts = 00 to 1638316383
    • Input range = 0–2.500 V
    • Temperature range = 0–200°C
    • Sensor output = 0–2.5 V linearly
    • Measured code at 100°C = 6550

    (i) Ideal LSB and Ideal Code at 100°C

    Step 1: Calculate ideal LSB

    A 14-bit ADC has:

    214=163842^{14}=16384

    quantization intervals.

    Therefore:

    LSB=2.50016384LSB=\frac{2.500}{16384}

    LSB=0.0001525879 VLSB=0.0001525879\text{ V}

    Hence:

    LSB≈152.59 μV\boxed{LSB\approx152.59\,\mu V}

    Step 2: Ideal voltage at 100°C

    The sensor is linear from 0 V at 0°C to 2.5 V at 200°C.

    At 100°C, which is half of the temperature range:

    V100=2.5×100200=1.25 VV_{100}=2.5\times\frac{100}{200}=1.25\text{ V}

    Step 3: Ideal ADC code

    Using the ideal ADC transfer convention:

    Codeideal=V100VFS(214−1)Code_{ideal}=\frac{V_{100}}{V_{FS}}(2^{14}-1)

    =1.252.5×16383=\frac{1.25}{2.5}\times16383

    =8191.5=8191.5

    So the ideal code is approximately:

    8192\boxed{8192}

    (ii) Offset Error

    Measured code:

    Codemeasured=6550Code_{measured}=6550

    Ideal code:

    Codeideal≈8192Code_{ideal}\approx8192

    Code error:

    ΔCode=6550−8192=−1642\Delta Code=6550-8192=-1642

    Convert this code error into voltage using the LSB:

    ΔV=ΔCode×LSB\Delta V=\Delta Code\times LSB

    =−1642×0.0001525879=-1642\times0.0001525879

    ΔV≈−0.25055 V\boxed{\Delta V\approx-0.25055\text{ V}}

    So the measured result is approximately 0.251 V below the ideal value.

    Equivalent temperature error

    The sensor has a range of:

    2.5 V↔200°C2.5\text{ V}\leftrightarrow200°C

    Therefore its sensitivity is:

    2002.5=80°C/V\frac{200}{2.5}=80°C/V

    Hence:

    ΔT=ΔV×80\Delta T=\Delta V\times80

    =−0.25055×80=-0.25055\times80

    ΔT≈−20.04°C\boxed{\Delta T\approx-20.04°C}

    Therefore, at the 100°C reference point, the calibrated reading corresponds to an error of approximately −20°C relative to the ideal transfer.

    Cross-check Using Measured Code

    Measured voltage corresponding to code 6550:

    Vmeasured≈6550×2.516384V_{measured}\approx6550\times\frac{2.5}{16384}

    ≈0.99945 V\approx0.99945\text{ V}

    This corresponds to:

    Tmeasured≈0.999452.5×200T_{measured}\approx\frac{0.99945}{2.5}\times200

    ≈79.96°C\approx79.96°C

    So a true 100°C input is being reported at approximately 79.96°C, giving an error of approximately:

    79.96−100≈−20.04°C79.96-100\approx-20.04°C

    Final Answer

    Quantity Result
    ADC resolution 14 bit
    Ideal LSB 152.59 μV
    Ideal code at 100°C ≈ 8192
    Measured code 6550
    Code error −1642 counts
    Offset error ≈ −0.2506 V
    Equivalent temperature error ≈ −20.04°C
    Measured temperature equivalent ≈ 79.96°C

    Note: Strictly, a single calibration point reveals a combined offset/gain error unless the gain is independently known. Under the exam's stated linear-sensor assumption, the difference at the 100°C reference is treated as the offset error.

  17. Q9(b). Write a short note on: Anti-aliasing filter20267m

    Module 2: Signal Conditioning Systems

    Write a short note on: Anti-aliasing filter

    View this question on its own page →
    Worked Solution

    Short Note: Anti-aliasing Filter

    An anti-aliasing filter is a low-pass filter placed before the ADC to remove signal components above half the sampling frequency (fs/2f_s/2), preventing aliasing.

    MermaidDiagram
    Rendering diagram…
    • Cut-off frequency is set at or just below fs/2f_s/2.
    • RC filter (first order): fc=1/(2πRC)f_c = 1/(2\pi RC), 20 dB/decade roll-off.
    • Higher-order Butterworth or Bessel active filters give sharper roll-off. Oversampling with a simple filter is an alternative.
    • Aliasing cannot be corrected after sampling, so the filter is essential.

    Exam tip

    Draw the block diagram and give the RC cut-off formula.